Standard Miura boiler noise is 85 dBA at the defined measurement point: 1 m vertically from boiler base level and 1 m horizontally from the front/control-cabinet end.
| Configuration | Typical table value |
| Standard | 85 dBA |
| With inlet silencer | 80 dBA for most listed models. Not available on the LX(N)(H)-250/300 models |
| With filter | Typically 85 dBA; 80 dBA listed for LX(N)(H)-300 |
| FGR | 85 dBA for listed EX models; not applicable to LX models |
- Values are equipment reference data, not a room sound-level guarantee.
- Room construction, multiple boilers, reflecting surfaces, ventilation equipment, and distance affect occupational exposure and measured sound.
- Confirm option availability for your exact model.